RMS-200v2 has six 24 bit
isolated voltmeters for sampling DC voltages up to 100 volts!
Overview
Each voltmeter is capable of measuring up to +/- 100 VDC with 24-bit accuracy.
When used in conjunction with the on board relays, a powerful voltage monitoring relay can be created.
Each voltmeter has its own 24 bit Delta Sigma ADC. The data and power lines for each voltmeter are
isolated with a chip-scale air core transformer. This enables each voltmeter to measure
different DC voltage sources without any effect on the main board or other voltages.
This technology enables the ability to measure (but not limited to):
- positive and negative voltages
- separate power sources
- individual batteries in a battery bank
- shunt voltages for equipment that may be drawing or generating power.
- solar panel voltage and amperage
- wind turbine voltage and amperage
- battery charger voltage and amperage
Setting the High and Low Voltage Jumpers
Each voltmeter has High Voltage and Low Voltage Mode Jumpers. In high voltage mode, the voltmeter has a range of +/- 100 VDC. In low voltage mode, the volmeter has a range of +/- 2.0 VDC and has over 4 million steps. This is perfect for measuring devices that output extremely low voltage ranges, in most cases however, low voltage mode is not needed. Each voltmeter has four configuration jumpers that set either high voltage or low voltage mode. On the PCB, for each voltmeter there are two sets of jumper pins marked HV and two marked LV. The RMS-200v2 boards are shipped with each voltmeter set to High Voltage mode. To set a voltmeter to Low Voltage mode, make sure the RMS board is powered off and there is no voltage hooked up to the voltmeter input, then simply remove both jumper shunts from the HV pins and move them to the corresponding LV pins as shown below. Power the RMS board back on. Under the voltmeter setup web page, uncheck the High Voltage Mode check box and hit save.
Note 1: WARNING improper settings of the high and
low voltage jumpers will damage the voltmeter inputs. Exceeding the maximum allowed voltage
will damage the voltmeter inputs. In high voltage mode, the maximum input voltage is +/- 100 VDC.
In low voltage mode, the maximum input voltage is +/- 2.0 VDC.
Any other jumper configuration except for what is shown above will damage the voltmeter inputs.
BEFORE changing jumper settings, always make sure that the RMS board is powered OFF AND
there is no voltage plugged into the voltmeter input.
Note 2: Voltmeters that have nothing hooked up to them so that the positive and
negative inputs are floating may read spurious positive and negative voltage readings, this
is normal. You may dampen the voltage reading by sacrificing accuracy using the precision
box. Use a number between 2 and 6 to increase or decrease the decimal place.
Note 3: Due to variations in components and the manufacturing process, voltmeter
readings may differ slightly from each other and from your hand held DVM. Use the
adjustment box to fine tune the voltmeter to display the expected value.
Web Interface
Below is a screen shot of the RMS-200v2 voltmeter overview page. This page shows at a glance all voltmeter readings and provides a gateway for more voltmeter options. In the screen shot below voltmeter 1 is displaying a positive reading of a 12v battery bank. Voltmeter 2 is in ammeter mode, it is measuring the charge going into the battery bank via a 50 millivolt / 50 amp current shunt (more on using shunts below). Voltmeter 3 is measuring the output of a negative 24 volt power supply. Note: A green bar graph indicates positive voltage, a red bar graph indicates negative voltage. The graphs button takes you to a page displaying voltage or amperage readings in a graph.Clicking on one of the voltmeter icons will bring you to the setup page for that particular
voltmeter. Below is a screen shot of the setup page for voltmeter one. Here you can enter
setup information like a name and notes for this voltmeter. The "Scale Mode Jumper" check
box lets the RMS-200v2 know if the mode jumper is installed or removed. The precision
box is used to set how many decimal places to display, valid choices are between 2 and 6.
The adjustment box is used to fine tune the voltmeter. The Polarity filter is used to
filter out unwanted positive or negative readings. The Polarity Filter will allow both
positive and negative, positive only, or negative only readings. The Polarity setting is
used to reverse the polarity of the voltage being read. The averaging filter will settle
the voltage bounce readings. The weight factor should be between 0 and 1. The larger the
number, the faster the answer is obtained. The lower the number, less bounce occurs. A good
default is 0.05 if the precision is set to 6. The averaging filter uses the formula
below.
C = w(C-P)+P
C = Current voltage reading
P = Previous voltage reading
w = Weight factor (as determined by value entered into the Weight Factor text box)
The "Suppress Trigger Actions on Boot" check box is used to stop actions from happening
when the RMS-200v2 board is warm or cold started, or when settings are changed. Each
voltmeter has a High, Normal, and Low trigger range. Each trigger range has a maximum and
minimum value. The range in between the maximum and minimum value acts like a dead band
area. Triggers can be set to fire alerts or scripts when the voltage is either too high or
too low. The High Trigger is used when the voltage rises above the High Trigger maximum
value. The Normal Trigger is used when the voltage falls below the High Trigger minimum
value. The "Execute Every" box is used to select how often the condition should be tested
and acted upon. Each voltmeter trigger can also execute a custom file stored on the
RMS-200v2 board.
Below is the Low Trigger interface. The Low Trigger is used when the voltage falls below
the Low Trigger maximum value. The Normal Trigger is used when the voltage rises above the
Low Trigger minimum value.
Voltmeter Triggers Explained
When a voltage is within a trigger range (as shown by the different color bands), the
action will only execute as often as specified by the "Execute Actions Below Every" pull
down list box. If a voltage is in the green (Normal Range), and moves above the High
trigger value (MIN) into the yellow, no actions occur. Only if the voltage moves into the
red range (past High Trigger Value (MAX)) will the action occur. If the voltage flutters
into the yellow and back into the red, this does not reset any triggers. The High Trigger
condition will reset only when the voltage falls back into the green where it will execute
the "High Normal Trigger" action only once.
The same theory applies to the Low Trigger values. If a voltage is in the green (Normal
Range), and moves below the Low trigger value (MIN) into the light blue, no actions occur.
Only if the voltage drops into the dark blue range (past Low Trigger Value (MAX)) will the
action occur. If the voltage flutters into the light blue and back into the dark blue, this
does not reset any triggers. The Low Trigger condition will reset only when the voltage
rises back into the green where it will execute the "Low Normal Trigger" action only
once.
Voltmeters on the Command Line
Below is an example of reading the voltmeters on the command line. Note: the
voltmeter readings are stored in files located in the /var/rmsdata folder. Voltmeter 1's
storage file is called vm1. Voltmeter 2's storage file is called vm2 etc.
Voltmeter Graphs
Each voltmeter has corresponding graphs associated with it. Below is a graph showing volts
over a 1 week period. Day, week, month, and year graphs are available.
Below is a graph showing voltmeter 4 in amperage mode. At one point during a 1 week period,
the solar panels were putting over 12 amps into the batteries.
How to Measure AC Voltage
The RMS-200v2 voltmeters can directly measure DC voltage from +/- 100 volts. To measure A/C voltage requires
an external simple to use piece of hardware called a transducer. To learn more about AC voltage transducers and how they work
see our
AC Voltage Project.
How to Measure DC Amperage using a Shunt
If you are managing a remote battery powered site, knowing your battery voltage is vital.
It is also a key thing to know how much charging you are putting back into your batteries,
and how much power is being consumed by your equipment. Using a common shunt, it is
possible to obtain a millivolt reading that relates to an amperage reading. The voltmeters
on the RMS-200v2 board are perfect for this as they are very sensitive and can easily
read millivolt readings.
A word on shunts.
Shunts are defined as a resistive load through which electricity is diverted. Often the
resistance of a shunt is known precisely and is used to determine amperage by measuring the
voltage drop across it using Ohm's law (I = V/R). It also allows high current measurements
with low-current equipment. Some popular shunts are 50mv/50amp and 100mv/100amp. The
relationship between the millivolt reading and the current going through the shunt makes
figuring out the amperage easy. For example, in the case of the 50mv/50amp shunt: if you
had 50 amps of charging going through the shunt then the millivolt reading would be 50mv.
If you had 25 amps of charging going through the shunt then the millivolt reading would be
25mv etc etc. When measuring current over 100 amps, continuous operating current should not
exceed 2/3 ammeter shunt rating. To ensure proper operation, the shunt temperature is in no
way to exceed 145°C, as a permanent change in resistance will occur. For example, if
continuous current for an application is 500 amps, the ammeter shunt rating should be no
less than 750 amps. This applies to both 50 and 100 millivolt current drop shunts.
To learn more about shunts and how much they cost, please visit: www.deltecco.com
Above is a drawing of a 50mv/50amp shunt.
So where does the RMS-200v2 fit into all of this?
Below is an example diagram of how to use RMS-200v2 with a shunt to measure charging
from a solar panel array. The negative solar panel lead is connected to the battery
negative terminal. The positive solar panel lead is routed to the positive battery terminal
by way of a 50 millivolt 50 amp current shunt. From one side of the shunt there is a sense
wire run to the negative input on VM4. From the other side of the shunt there is a sense
wire run to the positive input on VM4.
NOTE: Consult the Owners Manual or the Manufacturer of the equipment you are
measuring to determine if there is any preference on which power wire the shunt should be
hooked up to.
Below is a screen shot of how to setup Voltmeter 4 to act as an ammeter to show how much charging is going into the batteries from solar panels. First, put Voltmeter 4 into ammeter mode and click Apply. Next, enter valid shunt values (amperage rating, millivolt value). Set the precision to 5 or 6 decimal places. Enter the voltmeter name and notes and then click Apply or click Ok.
If everything is hooked up correctly you should be able to see how much amperage is being
put into your batteries. In the screenshot below the 12 volt main battery bank is being
charged by both solar and wind. This technique can be used to measure DC current being put
into your batteries by solar panels, a wind generator, or a battery charger. RMS-200v2
can monitor your voltage and amperage remotely and alert you to dangerous battery
conditions.
Below is an example of how to use RMS-200v2 with a shunt to measure current draw from
your equipment. The negative load wire is connected to the battery negative terminal. The
positive wire is routed to the positive battery terminal by way of a 50 millivolt 25 amp
current shunt. From one side of the shunt there is a sense wire run to the negative input
on VM4. From the other side of the shunt there is a sense wire run to the positive input on
VM4.
NOTE: Consult the Owners Manual or the Manufacturer of the equipment you are
measuring to determine if there is any preference on which power wire the shunt should be
hooked up to.
The electrical ratings for the voltmeter terminal blocks can be found here.
Need more Voltmeters? Add our USB Isolated Voltmeter Add-on Board.
RMS-200v2 is a remote voltage monitoring system with many features to give you the situational awareness to keep your equipment running reliably!
Our Story
EtherTek Circuits started its business in 2001. Ever since we have provided remote monitoring and control solutions for Remote Tower Sites, the Oil & Gas industry, Telemetry systems for Agriculture, Municipalities, Mines, Solar Farms, Hydro Plants, and the Military.